<lecture>
	<step>
		<caption>Introduction</caption>
		<video>./data/expts/ee004/expt4_Intro.flv</video>
		<description><![CDATA[<div class =tdText><ul><li>Schematic Diagram of a transformer with core and  windings.</li><li>Primary side takes the input voltage while put voltage is obtained at the secondary side.</li><li>Ratio of primary turns (N<sub>1</sub>) to secondary turns (N<sub>2</sub>)&nbsp;&nbsp; i.e. N<sub>1</sub>/N<sub>2</sub> is called turns ratio.</li><li>For step-up transformer N<sub>1</sub>&gt; N<sub>2</sub>, while for&nbsp;&nbsp; step-down transformer N<sub>1</sub>&lt; N<sub>2</sub>.</li><li>Need to first ascertain number of coils, voltage ratio and polarity of coil windings. </li></ul></div>]]></description>
	</step>
	<step>
		<caption>Run 1: Continuity Test</caption>
		<video>./data/expts/ee004/expt4_run01a_lecture.flv</video>
		<description><![CDATA[<div class =tdText><ul><li>Determine number of coils in primary and secondary.</li><li>Use multimeter to check continuity across coil terminals.</li><li>When the coils are continuous, the deflection is zero.</li><li>When the coils are discontinuous, the deflection is infinity.</li></ul></div>]]></description>
	</step>
	<step>
		<caption>Run 1: Voltage Ratio Test </caption>
		<video>./data/expts/ee004/expt4_run01b_lecture.flv</video>
		<description><![CDATA[<div class =tdText><ul><li>Nameplate shows 3KVA, 110:220V, 50Hz.</li><li>110V is the input voltage, while 220V is obtained at the output.</li><li>Apply 110V input across one primary coil and note voltage across the other coil terminals using the voltmeter.</li><li>Range of voltmeter used is 0-300V.</li><li>110V induced across the other primary coil and 220V across the secondary.</li></ul></div>]]></description>
	</step>
	<step>
		<caption>Run 1: Polarity Test</caption>
		<video>./data/expts/ee004/expt4_run01c_lecture.flv</video>
		<description><![CDATA[<div class =tdText><ul><li>Need to determine polarity of each coil before connecting coils in series or parallel.</li><li>Short any one terminal of one of the two primary coils with one terminal of the second coil, and measure the voltage between the other two terminals.  </li><li>If the terminals with opposite instantaneous polarity are shorted, there will be a series addition of voltage.</li><li>If the terminals with same instantaneous polarity are shorted, there will be a series subtraction of voltage.</li></ul></div>]]></description>
	</step>
	<step>
		<caption>Run 2: Parallel Operation</caption>
		<video>./data/expts/ee004/expt4_run02a_lecture.flv</video>
		<description><![CDATA[<div class =tdText><ul><li>For parallel operation with proper polarity, connect two primary coils  such that the dotted ends are shorted together, and the two undotted ends shorted together. </li><li>Parallel operation with incorrect polarity leads to a buildup of e.m.f.s across the primary coils, which leads to a circulating current within the closed path formed by the two coils.</li><li>5A Fuse used here blows off due to the circulating current.</li><li>Never connect coils with opposite polarity for parallel operation.</li></ul></div>]]></description>
	</step>
	<step>
		<caption>Run 2: D.C. Supply</caption>
		<video>./data/expts/ee004/expt4_run02b_lecture.flv</video>
		<description><![CDATA[<div class =tdText><ul><li>With D.C. supply, inductive reactance is absent in the primary ciruit(as frequency f = 0).</li><li>Coils generally have low resistance.</li><li>When connected to 110V D.C., low impedance leads to a high current that blows off the fuse.</li></ul></div>]]></description>
	</step>
	<step>
		<caption>Run 3: Loading of Transformer</caption>
		<video>./data/expts/ee004/expt4_run3_lecture.flv</video>
		<description><![CDATA[<div class =tdText><ul><li>Rated Current for Transformer = KVA Rating / Source Voltage = 3 KVA/110V = 30 A approx.</li><li>Use a fuse with  rating for minimum 30A ( i.e. have two or three 15A fuse wires in parallel). </li><li>Connect as a two winding step-up transformer, with two primary coils in parallel and connect the secondary side to a load box.</li><li>Load the secondary in steps of 2A, up to rated currentand measure the current in the primary and secondary using ammeters.</li></ul></div>]]></description>
	</step>
	<step>
		<caption>Run 4: Step Up Autotransformer</caption>
		<video>./data/expts/ee004/expt4_run4_lecture.flv</video>
		<description><![CDATA[<div class =tdText><ul><li>A single coil used as both primary and secondary.</li><li>Connect all the coils in series.</li><li>Input is 110V across one of the primary coils.</li><li>Output voltage can be measured across different terminals.</li></ul></div>]]></description>
	</step>
</lecture>